Power System Protections The steady-state operation of a power system is frequently disturbed by various faults on electrical equipment.To maintain the proper operation of the power system, an effective, efficient and reliable protection scheme is required.Power system components are designed to operate under normal operating conditions.However, due to any reason, say a fault, there is an abnormality, it is necessary that there should be a device which senses these abnormal conditions and if so, the element or component where such an abnormality has taken place is removed, i.e.deleted from the rest of the system as soon as possible.This is necessary because the power system component can never be designed to withstand the worst possible conditions due to the fact that this will make the whole system highly uneconomical.And therefore, if such an abnormality takes place in any element or component of the power system network, it is desirable that the affected element/component is removed from the rest of the system reliably and quickly in order to restore power in the remaining system under the normal condition as soon as possible.The protection scheme includes both the protective relays and switching circuits, i.e.circuit breakers.The protective relay which functions as a brain is a very important component.The protective relay is a sensing device, which senses the fault, determines its location and then sends command to the proper circuit breaker by closing its trip coil.The circuit breaker after getting command from the protective relay disconnects only the faulted element.this is why the protective relay must be reliable, maintainable and fast in operation.In early days, there used to be electromechanical relay of induction disk-type.However, very soon the disk was replaced by inverted cup, i.e.hollow cylinder and the new relay obtained was known as an induction cup or induction cylinder relay.This relay, which is still in use, possesses several important features such as higher speed;higher torque for a given power input an more uniform torque.However, with the advent of electronic tubes, electronic relays having distinct features were developed during 1940s.With the discovery of solid state components during 1950s, static relays with numerous advantages were developed.The use of digital computers for protective relaying purposes has been engaging the attention of research and practicing engineers since layer 1960s and 1980s.Now, the microprocessor/mini computer-based relaying scheme, because of its numerous advantages such as self –checking feature and flexibility, has been widely used in power system all over the world.The overall system protection is divided into following sections:(i)Generator protection,(ii)Transformer protection,(iii)Bus protection,(iv)Feeder protection,(v)Transmission line protection.Basic Requirements to Protective Relays Any protection scheme, which i.e.required to safeguard the power system components against abnormal conditions such as faults, consists basically of two elements(i)Protective relay and(ii)Circuit breaker.The protective relay which is primarily the brain behind the whole scheme plays a very important role.Therefore proper care should be taken in selecting an appropriate protective relay which is reliable, efficient and fast in operation.The protective relay must satisfy the following requirements: ⑴ since faults on a well designed and healthy system are normally rare, the relays are called upon to operate only occasionally.This means that the relaying scheme is normally idle and must operate whenever fault occurs.In other words, it must be reliable.⑵ Since the reliability partly depends upon the maintenance, the relay must be easily maintainable.⑶ The palpation of the relay can be in two ways.One is the failure to operate in case a fault occurs an second is the relay operation when there is no fault.As a matter of fact, relay must operate if there is a fault and must not operate if there is no fault.⑷ Relaying scheme must be sensitive enough to distinguish between normal and the faulty system.Protective Relays The function of the protective relay is to sense the fault and energize the trip coil of the circuit breaker.The following types of the protective relays are used for the apparatus such as synchronous machines, bus bar, transformer and the other apparatus and transmission line protection.(1)Over current relays,(2)Under voltage relays,(3)Under frequency relays,(4)Directional relays,(5)Thermal relays,(6)Phase sequence relays such as(i)negative sequence relays and,(ii)zero sequence relays,(7)Differential relays and percentage differential relays,(8)Distance relays such as(I)plane impedance relays,(ii)angle impedance relay, i.e.Ohm or reactance relays,(iii)angle admittance relays,i.e.Mho relays and ,(iv)offset and restricted relays,(9)Pilot relays such as(i)wire pilot relays,(ii)carrier channel pilot relays,(iii)microwave pilot relays.There are different types of the relaying scheme based on construction.They are:(i)electromechanical type,(ii)thermal relays,(iii)transduction relays,(iv)rectifier bridge relay,(v)electronic relays,(vi)digital relaying schemes.电力系统继电保护

电力系统的稳态运行经常会因各种电力设备配故障原因而被扰乱。为了保证电力系统可靠运行,有效的、充足的、可靠的保护机制是必不可少的部分。电力系统元件通常是按照在正常工作条件下 运行。然而,由于任何原因,比如说故障,出现非正常运行状态,有必要采用一个装置来感知这种 非正常状态,然后这种出现非正常状态的元件可以被切除,也就是说,尽可能快地将该元件与系统 其它部分隔离。这是必须的,因为现实情况下,为避免造成很大的经济损失,电力系统元件并未按 照故障运行情况下的耐受程度设计。因此,如果电网当中的任何元件发生异常状况,受影响的元件 将会同其余部分可靠快速的切除,以便于电力系统在正常工作条件下尽可能快的恢复。

保护体系包括包括保护继电器以及跳合闸回路,例如,断路器。继电包括就如同大脑的作用一 样,是十分重要的。保护继电器是一个感知元件,它感知故障、确定故障的位置,并且通过闭合相 应断路器的跳闸线圈来发出跳闸命令。断路器在接收到保护继电器的命令之后切除故障元件。这就 是为什么保护继电器必须可靠、快速的运行。

以前,常用的电磁继电器是一种电感性质的,不久就被一种反转型的替代。例如将中空的圆筒 和新型保护继电器做成一种为人们所知的电感型的或者磁感应继电器。这种继电器至今还被延用,并且拥有很多种重要特性,例如高速、大转矩作为能量输入以及更多的均衡的转矩。

然而,1940 年,电子管的出现,使电力继电器的特性得到很快的发展。1950 年,伴随着固态元 件的发现,静态继电器的许多优点有又被得以很好的发展。1960 年至 1980 年,计算机被用于继电 器保护中,它能很好的参与并在实践中得到很好的利用。当今,微机或者袖珍型计算机已经成为了 继电保护的主题,由于其自身有很多的优点例如自检功能和强的适应能力,所以,它现在已经广泛 的被用于全球的电力系统。

全球的的电力系统保护分为以下几个部分 :(1)发电机保护;(2)变压器保护;(3)母线保护;(4)馈线保护;(5)输电线路保护。

保护继电器的基本构成

任何一种保护,均被用来保护电力系统异常情况下发生的故障,它包括两个基本元件分别是(1)保护继电器;(2)断路器。保护继电器在保护当中起着十分重要的作用。因此在选择合适的继电器 时应当投入相当大的精力,以满足继电器在运行中的可靠性、快速性、灵敏性。保护继电器必须满 足下列条件。⑴任何设计完善能够正常运行的系统都或多或少的存在少许的问题,因此这就要求保护继电器 动作的灵敏性要高。这就是说继电保护系统平常是空载运行的但无论何时一旦有故障发生必须运行。胡句话说,它应当有相当的可靠性。⑵可靠性很大的程度上取决于它是否易于维护,因此,继电器应当便于维护。⑶继电器的误操作有两种可能,一种是故障发生时运行失败,另一种是系统正常运行时,继电 器动作。现实运行中要求,继电器在故障时必须可靠动作,在无故障是必须可靠不动作。

⑸ 保护系统必须能够具有充足的灵敏性去判断区分故障系统与正常运行系统。

保护继电器

继电器的作用是感应故障并与断路器配合工作。同步奠基,母线,变压器,其他电气设备和输电线路保护中通常使用下列几种继电器。

(1)过流继电器,(2)过压继电器,(3)低频继电器,(4)方向继电器,(5)温度继电器,(6)相序继电器例如负序继电器以及零序继电器,(7)差动继电器和比率差动继电器,(8)距离继电器,包括平面阻抗继电器,角度阻抗继电器如欧姆或阻抗继电器,角度导纳继 电器如母欧继电器,偏置继电器等。

(9)控制继电器,例如有线控制继电器,载波控制继电器,微波控制继电器。继电保护按照结构可分为很多不同的种类。分别是:电磁继电器,热继电器,整流桥型继电器,电子继电器,静态继电器,数字式保护继电器。

篇2:电力系统继电保护外文及翻译

继电保护外文英语参考文献

文章类型:参考文献参考文献格式本文是一篇参考文献,对于很多研究继电保护这一专业的学生们来说,参考文献的选择尤其重要,参考文献主要考察的就是同学们对这行业的研究水平以及掌握的知识范围,现为方便广大此专业的`学生们,今统计整理了部分最新的继电保护的英语参考文献,希望可以帮助到大家。[1]Abhishek Khanna. Analysis of High Impedance Protection Considering CT-Transients and Air Gapped CTs with Setting Recommendations and a New Fast Acting Algorithm for High Impedance Numerical Relays[J]. International Journal of Emerging Electric Power Systems,,12(1):.[2]Mojtaba Khederzadeh. Mechanical Protection of Induction Motors by Off-the-Shelf Electrical Protective Relays[J]. International Journal of Emerging Electric Power Systems,2011,12(2):.[3]El Sayed M. Tag Eldin. A Novel Approach for Classifying Transient Phenomena in Power Transformers[J]. International Journal of Emerging Electric Power Systems,2011,1(2):.[4]J. Havelka,R. Malari?,K. Frlan. Staged-Fault Testing of Distance Protection Relay Settings[J]. Measurement Science Review,,12(3):.[5]Xiong Haijun,Zhang Qi. A New Method for Setting Calculation Sequence of Directional Relay Protection in Multi-Loop Networks[J]. International Journal of Emerging Electric Power Systems,,17(4):.[6]Si Tuyou,Wu Jiekang,Yuan Weideng,Du Anan. Power supply risk assessment method for relay protection system faults[J]. Archives of Electrical Engineering,2016,65(4):.[7]Elmer Sorrentino. Analysis of overtravel in induction disc overcurrent relays[J]. Electric Power Systems Research,2016,:.[8]Stanislav Misak,Jindrich Stuchly,Jakub Vramba,Tomas Vantuch,David Seidl. A novel approach to adaptive active relay protection system in single phase AC coupling Off-Grid systems[J]. Electric Power Systems Research,2016,131:.[9]Rahul Dubey,S.R. Samantaray,B.K. Panigrahi. Data-mining model based adaptive protection scheme to enhance distance relay performance during power swing[J]. International Journal of Electrical Power and Energy Systems,2016,:.[10]Manoj Thakur,Anand Kumar. Optimal coordination of directional over current relays using a modified real coded genetic algorithm: A comparative study[J]. International Journal of Electrical Power and Energy Systems,2016,:.[11]Miodrag Forcan,Zoran Stojanovi?. An algorithm for sensitive directional transverse differential protection with no voltage inputs[J]. Electric Power Systems Research,2016,:.[12]Oleg Sivov,Hany Abdelsalam,Elham Makram. Adaptive setting of distance relay for MOV-protected series compensated line considering wind power[J]. Electric Power Systems Research,2016,:.[13]S.A. Ahmadi,H. Karami,M.J. Sanjari,H. Tarimoradi,G.B. Gharehpetian. Application of Hyper-Spherical Search Algorithm for Optimal Coordination of Overcurrent Relays Considering Different Relays Characteristics[J]. International Journal of Electrical Power and Energy Systems,2016,:.[14]Ahmed R. Adly,Ragab A. El Sehiemy,Almoataz Y. Abdelaziz. A negative sequence superimposed pilot protection technique during single pole tripping[J]. Electric Power Systems Research,2016,:.[15]L.A. Trujillo Guajardo. Prony filter vs conventional filters for distance protection relays: An evaluation[J]. Electric Power Systems Research,2016,:.[16]Zohaib Akhtar,Muhammad Asghar Saqib. Microgrids formed by renewable energy integration into power grids pose electrical protection challenges[J]. Renewable Energy,2016,:.[17]A.M. Ibrahim,W. Elkhatam,M. Mesallamy,H.A. Talaat. Adaptive Protection Coordination Scheme For Distribution Network with Distributed Generation using ABC[J]. Journal of Electrical Systems and Information Technology,,:.[18]Ricardo C. Santos,Simon Le Blond,Denis V. Coury,Raj K. Aggarwal. A novel and comprehensive single terminal ANN based decision support for relaying of VSC based HVDC links[J]. Electric Power Systems Research,2016,:.[19]Meng Yen Shih,Arturo Conde Enríquez,Tsun-Yu Hsiao,Luis Martín Torres Trevi?o. Enhanced differential evolution algorithm for coordination of directional overcurrent relays[J]. Electric Power Systems Research,2016,:.[20]Fernando B. Bottura,Wellington M.S. Bernardes,Mário Oleskovicz,Eduardo N. Asada. Setting Directional Overcurrent Protection Parameters using Hybrid GA Optimizer[J]. Electric Power Systems Research,2016,:.[21]Mazen Abdel-Salam,Rashad Kamel,Khairy Sayed,Mohsen Khalaf. Design and implementation of a multifunction DSP-based-numerical relay[J]. Electric Power Systems Research,,143:.[22]Elmer Sorrentino. Behavior of induction disc overcurrent relays as a function of the frequency[J]. Electric Power Systems Research,2016,:.[23]Emilio C. Piesciorovsky,Noel N. Schulz. Comparison of Non-Real-Time and Real-Time Simulators with Relays In-The-Loop for Adaptive Overcurrent Protection[J]. Electric Power Systems Research,2016,:.[24]Akbar Sharafi,Majid Sanaye-Pasand,Farrokh Aminifar. Transmission System Wide-area Back-up Protection using Current Phasor Measurements[J]. International Journal of Electrical Power and Energy Systems,2017,:.[25]Min Zhu,Wei Dong Liu,Wen Song Hu. Application of Fuzzy Neural Network in Relay Protection[J]. Advanced Materials Research,2011,1100(181):.[26]Wei Kang,Xing Chen,Jian Ting Gui,He Zhang,Li Xia Zhang. Research on Microcomputer Relay Protection Anti-Interference of 500kV Transmission Line in MATLAB[J]. Advanced Materials Research,2011,1158(204):.[27]Wei Ming Guo,Gan Qing Zuo,Rui Lin. The Analysis of the Opto-Couplers Relay Malfunctions in HVDC Control and Protection and the Improvements of the Trip Circuits[J]. Advanced Materials Research,2012,1478(354):.[28]Shi Qi Liu,Huan Wang,Xiao Ming Li,Dong Xu Zhou. The Research on High-Voltage Transmission Line Relay Protection Setting Related to OLTC Anti-Icing[J]. Advanced Materials Research,2012,1518(383):.[29]Xiao Ming Li,Sha Li,Peng Lu,Shu Qiong Liu. The Study on Configuration and Setting of Relay Protection when Distributed Generation Accesses to Distribution Network[J]. Advanced Materials Research,2012,1566(433):.[30]Shi En He,Xin Zhou Dong,Zhi Qian Bo,Jia Le Suo Nan. The Relay Protection Scheme for Distribution Network with Distributed Generations[J]. Advanced Materials Research,2012,1566(433):.[31]Jing Jing Zhang. Research and Summary on Reliability of Relay Protection System[J]. Advanced Materials Research,2012,1566(433):.[32]Li Kai Liang,Yu Yin Zhang,Xiao Cong Zhang. Research on Programmable Logical Relay Protection[J]. Applied Mechanics and Materials,2012,2034(229):.[33]Pei Ding,Fei Guo,Xu Tao Wu,Xiu Guang Li,Zhen Hua Yan,Zhi Guo Hao. New Development in Relay Protection for Smart Grid – Protection Function Development[J]. Applied Mechanics and Materials,,2279(291):.[34]Xu Cen,Shu Ming Liu,Qiong Lin Li,Shun Tao. Influence of Harmonic on the Protections of Capacitor Bank[J]. Applied Mechanics and Materials,2013,2279(291):.[35]Yu Tian Zhou,Yun Wu,Tong Zuo. Research on Decision Support System of Relay Protection Equipment Status Evaluation Based on Mechanical Overhaul[J]. Applied Mechanics and Materials,2013,2549(345):.[36]Jian Xu,Xin Yao. Research and Improvement of Fourier Algorithm in the Microcomputer Relay Protection[J]. Applied Mechanics and Materials,2013,2560(347):.[37]Zong Jiang Mu,Yan Xu,Shao Bo Yan. Risk Assessment of Relay Protection Setting Value in Power Plant[J]. Applied Mechanics and Materials,2013,2594(373):.[38]Zong Jiang Mu,Yan Xu,Xing Dong Qiu,Jin Jie Wang. On-Line Verification of Relay Protection Setting Based on Transmission Contribution Degree[J]. Applied Mechanics and Materials,2013,2594(373):.[39]Huan Ren,Yan Xu,Qing Jie Zhou. Research on Condition Evaluation Method of Relay Protection Based on Reliability Indices[J]. Applied Mechanics and Materials,2013,2594(373):.[40]Lei Dong,Wei Di Li,Wen Ping Zhou,Tian Jiao Pu. Relay Protection Security Analysis of Jiuan Substation under Complex Power Transmission Environment[J]. Applied Mechanics and Materials,2013,2601(385):.[41]Pan Zhang,Yan Xia Zhang,Wen Bo Xuan,Hong Yuan Zhang,Bin Bn Tian. Study on Simulation System of Relay Protection for Smart Substation[J]. Applied Mechanics and Materials,2013,2601(385):.[42]Zhi Feng Peng,Ming Yu Yang,Qing Jie Zhou,Cheng Yong Yuan. Analysis about Random Failure Indicator for Relay Protection[J]. Applied Mechanics and Materials,2013,2635(391):.[43]Rui Li,Shu Yong Song,Zhen Guo Ma,Zi Ming Kou. Design of Setting Management System of Relay Protection to Anti-Grade Trip in Coal Mine Based on Serial Communication[J]. Applied Mechanics and Materials,2013,2701(415):.[44]Vinay Barhate. Generating Various Inverse Time over Current Numerical Relays Using Microcontroller for Power System Protection[J]. Applied Mechanics and Materials,2013,2701(415):.[45]Qian Rui,Su Qin Qian. Relay Protection Based on Multi-Agent System[J]. Advanced Materials Research,2013,2542(760):.[46]Rui Li,Shu Yong Song,Hui Ping Zheng,Zhen Guo Ma,Hui Yong Li,Tong Yu Zhang. Design on Synchronize Debugging Device for Extra High Voltage Transmission Line Longitudinal Protection[J]. Advanced Materials Research,2013,2694(805):.[47]Xue Song Zhou,Chun Ji,You Jie Ma. Review of STATCOM Effects on Relay Protection of Power System[J]. Advanced Materials Research,2013,2690(811):.[48]Jian Ping Jia. The System Design and Simulation Research of Low Voltage Lockout over Current Protection about Transmission Line[J]. Advanced Materials Research,2013,2731(823):.[49]Tao Wang,Gui Hua Lin,Dong Han. Research of Single-Device Test Based on Relay Protection Simulation and Training System[J]. Applied Mechanics and Materials,,2948(496):.[50]Hui Sheng Gao,Hui Fang Wang. Searching Path for Delay Protection Services of Fiber Channel Based on Security and Risk Equalization[J]. Applied Mechanics and Materials,2014,2948(496):.[51]Xin Chao Wang,Chen Xin Yang. A Study on DG Control Strategy and Grid Protection[J]. Applied Mechanics and Materials,2014,3012(521):.[52]Yong Zhang. Study on Relay Protection Technology in Power System[J]. Applied Mechanics and Materials,2014,3012(521):.[53]Nan Nan Gao,Lin Niu,Ying Pei,Hong Bo Li,Jie Zhan. Design and Application of Analysis Software for Relay Protection Action Based on PAS[J]. Applied Mechanics and Materials,2014,3082(543):.[54]Hao Ran Xue,Bin Li,Kun Ji,Zhi Qiang Wang,Xiao Jun Kong. The Optimization Methods Based on Big Data Technologies of Power System Protection[J]. Advanced Materials Research,2014,3135(918):.[55]Peng Fei Shi,Yu Jiong Gu,Wei Lin Zhang,Kun Yang. Protection of the Island Microgrid Based on Ocean Energy[J]. Advanced Materials Research,2014,3249(953):.[56]Nian Fang,Xian Shan Li,Hao Xu,Yu Long Du. Relay Protection Setting Calculation and Analysis of Auxiliary Power System for Hydropower Plants[J]. Applied Mechanics and Materials,2014,3296(574):.[57]Fen Fen Chen,Shi Wu Xiao. Micro-Grid Fault Transient Characteristics and Relay Protection[J]. Advanced Materials Research,2014,3294(986):.[58]Peng Fei Hu,Yu Xiang Yuan,Zhi Juan Qu,Xue Ping Jiang. System on Chip Design for Multi-Principle of Relay Protection in the FPGA[J]. Applied Mechanics and Materials,2014,3590(668):.[59]Gui Hua Lin,Yu Ying Wang,Tao Wang. Research on Bus Coupler Charging Protection Problem[J]. Applied Mechanics and Materials,2014,3546(672):.[60]Zi Nan Liu,Shi Wu Xiao,Shan Jiang. Research on Evaluation Method of Relay Protection Action Based on Fault Information[J]. Advanced Materials Research,2014,3530(1044):.[61]M.V. Andreev,A.S. Gusev,A.O. Sulaymanov. Testbed Based on Hybrid Real-Time Power System Simulator for Setting up and Testing of Protection and Control Systems[J]. Applied Mechanics and Materials,2015,3676(698):.[62]Hua Bo Shi,Zhi Chen,Gan Li,Bo Zhou. Research on Short-Circuit Current of Wind Power System and its Impact on Relay Protection[J]. Advanced Materials Research,2015,3701(1070):.[63]Peng Sun,Ming Wu Luo,Zhao Xia Sun,Tian Ci Liu,Chang Hong Deng,Lei Chen,Hao Pan,Feng Zheng. Penetration Capacity Analysis of Distributed Generation Considering Overcurrent Relay Protection and Flux-Coupling Type FCL[J]. Advanced Materials Research,2015,3701(1070):.[64]Shu Zheng,Zhi Hua Xu,Jia Jia Liu,Qiang Fu. The Application of Electronic Communication Relay Protection in Distribution Network with Distributed Generation[J]. Advanced Materials Research,2015,3701(1070):.[65]Zhi Gen Xiao,Jie Tong,Yang Wang,Xi Gao. Research on Field Management of Relay Protection Device Based on RFID Technology[J]. Advanced Materials Research,2015,3701(1070):.[66]Wei Wei,Wei Zhen,Ming Zhong Liu,Xiao Bin Liang,Cang Yang Chen. Research on Error Characteristic of the Protective Current Transformer in High Remanence Environment[J]. Advanced Materials Research,2015,3701(1070):.[67]Hong Lei Tian,Jian Feng Liu,Yong Kuan Liu,Yuan Fang,Wen Huai Chen,Liang Gao. The Research on Relay Protection Settings On-Line Verification System Application in Smart Grid[J]. Advanced Materials Research,2015,3701(1070):.[68]Yan Jie Zhang,Zhi Heng Xu,Hai Bo Zhang,Xing Qiao Wang,Xue Hua Shi. A Test Rig for Smart Substation Training System[J]. Applied Mechanics and Materials,2015,3749(719):.[69]Hui Hai Liu,Xiao Li Zhang,Wei Li,Xiao Yang Wang,Yi Fan Zhang. Research on Relay Protection of Distribution Network System with Distributed Generation[J]. Applied Mechanics and Materials,2015,3827(734):.[70]Guang Xian Shao,Jun Lu,Hao Yu. Design and Research of Relay Protection Fiber Channel Intelligent Management System[J]. Applied Mechanics and Materials,2015,3785(738):.[71]Ming Jong Lin. Critical Clearing Time Associate with Relation of Power Load Factor and Frequency in Transient Stability[J]. Applied Mechanics and Materials,2015,3862(743):.[72]John Morales,Marco Carpio. Induced Lightning Stroke Identification on Protection Relays[J]. Applied Mechanics and Materials,2015,4058(775):.[73]Nor Zulaily Mohamad,Ahmad Farid Abidin,Ismail Musirin. Adaptive Distance Protection to Prevent False Relay Tripping during Power Swing[J]. Applied Mechanics and Materials,2015,4079(785):.[74]Abadal Salam T. Hussain,Waleed A. Oraibi,Fadhel A. Jumaa,F. Malek,Syed F. Ahmed,Taha A. Taha,Jailani O. Mahmoud,Nur Fairuz Mohamed Yusof,Mohd Irwan Yusoff,Muhammad Irwanto Misrun,Gomesh Nair Shasidharan. Power Plant Station Protection System against Voltage Fluctuation[J]. Applied Mechanics and Materials,2015,4172(793):.[75]Indra Nisja,M.H. Idris,M. Syafrudin,S. Hardi,M. Isa. The Effect of Harmonic Distortion on the Performance of Differential Relay for Distribution Transformer Protection[J]. Applied Mechanics and Materials,2015,4172(793):.[76]Sang-Cheol Lee,Young Gui Lee,Hae-Gweon Kang,Tai-Ying Zheng,Yong-Cheol Kang. Distance Relay Suitable for Intertie Protection of a Large Wind Farm[J]. Journal of International Council on Electrical Engineering,2012,2(3):.继电保护英语参考文献三:[77]Ge Liang,Wang Liding,Yang Changfu,Zhou Shuxiong. Protection Relay and Fault Information Analyzing System for Smart Grid[J]. Journal of International Council on Electrical Engineering,2013,3(2):.[78]Myeong-Hee Lee,Cha-Soo Park. The Protection System Optimization of 154kV Shunt Capacitor Bank in Korea[J]. Journal of International Council on Electrical Engineering,2013,3(2):.[79]Jianzhong Wang,Jibin Cui,Zhiquan Xiong,Meirong Zi. The Research of Relationship between SICSFCL and Distance Relay Protection of Power Grid[J]. Journal of International Council on Electrical Engineering,2012,2(2):.[80]Ashok Manori,Manoj Tripathy,Hari Om Gupta. Advance Compensated Mho Relay Algorithm foraTransmission System with Shunt Flexible AC Transmission System Device[J]. Electric Power Components and Systems,2014,42(16):.[81]Lijie Huo,Bing Li,Xuan Hu,Chunsong Liu. Research on Motor Relay Protection of High-Voltage Variable Frequency Motor Drive System[J]. Journal of International Council on Electrical Engineering,2014,4(4):.[82]Ahmed H. Osman,Mohamed S. Hassan,Mohamad Sulaiman. Communication-based Adaptive Protection for Distribution Systems Penetrated with Distributed Generators[J]. Electric Power Components and Systems,2015,43(5):.[83]S. Sengupta. A Microprocessor-Based High-Speed Relay for Protection of Parallel EHV/UHV Feeders Using Waveform Comparison Technique[J]. Electric Power Components and Systems,,31(9):.[84]M. A. L. Badr,S. Mahrous,M. B. Eteiba. LOSS OF FIELD SOLID STATE RELAY FOR PROTECTION OF SYNCHRONOUS MACHINES[J]. Electric Power Components and Systems,1993,21(5):.[85]Xin-ke Gao,Ya-peng Liu. Influence of the inverse-time protection relays on the voltage dip index[J]. Journal of Shanghai Jiaotong University (Science),2014,19(3):.[86]E. Sutlovi?,K. Petric. RELAY PROTECTION DATABASE[J]. Journal of Energy,,56(5):.[87]Srete Nikolovski,Vanja Papuga,Goran Kne?evi?. Relay Protection Coordination for Photovoltaic Power Plant Connected on Distribution Network[J]. International Journal of Electrical and Computer Engineering Systems,2014,5(1):.[88]Zhaoyun Zhang,Wei Chen,Zhe Zhang. Research on the relay protection system of micro-grid[J]. Technical Gazette,2015,22(1):.[89]Yu S Borovikov,A O Sulaymanov,M V Andreev. Application of Hybrid Real-Time Power System Simulator for Designing and Researching of Relay Protection and Automation[J]. IOP Conference Series: Materials Science and Engineering,2015,93(1):.[90]Mahesh Praveenkumar,Mugundhan Hayagrivan,Badrinarayanan Rajagopalan. Ferrofluid Actuated Thermal Overload Relay[J]. Smart Grid and Renewable Energy,2012,03(01):.[91]A.S. Khraiwish,M. Alshamasin,R. Kassasbeh,Y. Al shiboul,Z. Al-Qudah,M. Al-Busoul. The Effect of the Harmonics, the Fault Location and the Fault Resistance on the Performance of the Impedance-Type Distance Relay[J]. American Journal of Applied Sciences,,6(4):.[92]Anonymous. Megger; Megger: Enhance Your Relay and Protection Knowledge - Free![J]. Computers, Networks & Communications,2011,:.[93]El Sayed Tag Eldin. A Novel Approach for Classifying Transient Phenomena in Power Transformers[J]. 国际新兴电力系统期刊,,1(2):.

篇3:电力继电保护系统故障检修及应用

1 进行电力继电保护系统故障检修及应用的重要意义

为了保证电力继电保护系统有效的发挥作用, 就很有必要对电力继电系统存在的问题进行检测和维修工作。随着人民群众生活水平的逐步提升, 人民群众对于用电质量的要求也逐步提升, 这也对电力继电保护系统故障的排除提出了更多的要求。针对这样的情况, 本文将具体结合电力继电保护系统的工作原理和电力继电保护系统出现故障的原因, 提出电力继电保护系统故障检修策略和发展方向。

2 继电保护系统工作原理及基本构成

2.1 继电保护系统工作原理

电力继电保护系统的工作原理是根据电力系统出现的电力数值改变而产生的电力继电系统的自我调节功能 (例如, 当电力系统之中的电流数值出现异常变化、电力系统之中的电压数值发生忽然变化、电力系统的电力频率发生变化、电力系统输电线路的温度突然上升等) 。与此同时, 无论电力系统之中的机电保护系统是出于什么样的工作状态, 存在的前提都是要保证整个电力系统可以处于安全的运行状态。

2.2 继电保护系统基本构成

电力继电保护系统经过多年的发展, 已经发展到了微机型的继电保护系统的状态, 这种类型的继电保护系统主要包括三个组成部分:第一个组成部分是电力系统信号采集部分, 这一部分的主要功能是将电力系统内部的电力数值情况收集整理, 将各种电力参数有效的传递给电力系统的继电保护部分;第二个组成部分是电力系统的信号处理部分, 这一部分的主要功能是将电力系统信号采集部分收集到的信号进行有效的处理, 并按照一定的方式将出现的问题进行归类处理;第三个组成部分是信号输出部分, 这一部分的主要功能是将输出的信号指令准确的传递到电力系统之中去, 完成调节部分的工作运行。

3 继电保护系统故障分析排除策略

3.1 使用回路拆除法排除继电保护系统故障问题

由于二次回路故障问题是电力继电保护系统很容易出现的问题, 与此同时, 有效的确定二次回路故障问题出现的位置是解决这一故障问题的关键部分。针对这样的情况, 可以使用回路拆除法排除继电保护系统故障问题。具体的来说, 就是在检查电力继电保护系统的过程之中, 首先按照二次回路的顺序进行对电力继电保护系统的拆除工作, 在逐步的将拆除下来的部分安装回去, 最终有效的找出故障存在的位置, 解决继电保护系统故障问题

3.2 使用短接法排除继电保护系统故障问题

为了有效的找出继电保护系统故障存在的位置, 在进行故障检测的过程之中, 可以将电力继电保护系统按照一个回路作为一个段, 逐次的采用短接处理的方式, 找出继电保护系统存在故障的位置, 进而有效的解决继电保护系统故障问题。

3.3 使用替换法排除继电保护系统故障问题

在解决电力继电保护系统的故障问题的时候, 可以使用替换法将电力机电系统之中有着故障可能的元件替换下来, 通过这样的方式, 可以较为快速的解决继电保护系统之中存在的故障问题。一般情况下, 由于采用替换法相对比较简单快捷, 该方法一般使用在会电力继电系统内部构造比较复杂的情况之下。

3.4 使用对比参照法法排除继电保护系统故障问题

如果电力继电保护系统出现故障的原因是由于安装的技术人员出现的技术失误, 就可以使用对比参照法法排除继电保护系统故障问题。具体的来说, 就是参照已经安装好的可以正常使用的继电保护系统的内部线路的基本构造, 找寻出该继电保护系统之中存在的问题所在。

4 继电保护系统常见故障种类

4.1 继电保护系统电压互感器的二次回路故障问题

继电保护系统的核心组成部分就是系统的电压互感器部分, 这一部分发挥着排除电力系统之中过高电压的作用。一般情况下, 电压互感器会承受着相对数值比较大的电阻负载, 与此同时, 电压互感器上所承受的的二次电压的数值和所承受的一次电压的数值有着正比例关系, 如果在这样的背景下, 出现了电阻数值下降的情况, 就很有可能导致电压互感器出现短路问题。

一般情况下, 电压互感器出现故障问题主要集中出现在开口的三角电压的数值不稳定之上, 由于电压互感器内部的铁芯之中很容易因为电压的升高而出现线性不稳的问题, 因此, 面对这种故障问题的时候, 就需要注意电压互感器的回路短路问题。

4.2 继电保护系统电流互感器的故障问题

由于继电保护系统内部的电流互感器是通过电磁感应原理而制作完毕的, 电流互感器存在的主要作用也是将原先数值较大的电流转换成为数值较小的电流。针对这样的情况, 不难看出, 如果电流互感器内部的绝缘部分出现破裂的问题, 就很有可能会出现电流窜出等问题, 严重影响到电力系统的正常运行。

4.3 计算机型继电保护装置的故障问题

随着信息科学技术的不断进步, 计算机技术已经开始融入进入继电保护系统之中, 但是, 在具体的运行过程之中, 一旦出现输入功率不足的问题, 很有可能导致计算机系统控制输出的电压数值下降的问题, 影响到电力系统电力数值的正常运行。

5 故障诊断技术的发展方向

根据上文之中对继电保护系统运行工作原理的分析说明, 已经知道了继电保护系统运行是根据电力系统内部的电力数值变化而存在的, 这就要求要尽可能的保证电力继电保护系统可以知晓电力系统内部具体的电力数值信息的变化情况, 保证电力继电保护系统可以调节电力数值协调的满足电力系统的需要。与此同时, 随着信息科学技术的不断发展, 利用先进的信息科学技术就可以满足上述的需要。

在未来的继电保护系统故障问题的解决过程之中, 会尽可能的向微处理器自动控制的方向发展。具体的来说, 一旦继电保护系统出现问题, 微处理器系统就会自动切除故障部位的线路, 以便于保证其他线路的正常运行, 通过人工智能的方式, 实现对继电保护系统故障的有效排除。

综上所述, 电力继电保护系统在电力系统之中发挥着重要作用, 为了保证电力系统的正常运行, 很有必要随时排除电力继电保护系统之中存在的故障问题。与此同时, 电力继电保护系统容易出现的故障问题主要包括二次回路故障和电流互感器故障, 针对这几种容易出现的故障, 本文也作出了较为详细的解决处理方式的解答, 希望能够通过分析电力继电保护系统之中存在的故障问题, 找寻出可行的解决方案, 并不断总结出故障诊断技术的发展方向。

参考文献

[1]冯海东, 陈奕琴.谈继电保护故障处理的九种方法[J].广东科技, 2008 (20) .

[2]王海军.电力系统继电保护技术的探析[J].内蒙古煤炭经济, 2011 (02) .

篇4:电力系统继电保护技术及配置应用

本文作者主要就我国电力系统继电保护技术的发展现状、继电保护的配置及发展趋势做了阐述,同时对智能电网继电保护装置简介、维护及实际应用进行了探讨。

论文关键词:继电保护 配置应用 维护 发展

1.前言

近年来,随着电子及计算机通信技术的快速发展为继电保护技术的发展注入了新的活力,同时也给继电保护技术不断的提出了新的要求。作为继电保护技术如何才能有效的遏制故障,使电力系统的运行效率及运行质量得到有效的保障,是继电保护工作技术人员需要解决的技术问题。

2.继电保护发展现状

20世纪60-80年代是晶体管继电保护技术蓬勃发展和广泛应用的时期。70年代中期起,基于集成运算放大器的集成电路保护投入研究,到8O年代末集成电路保护技术已形成完整系列,并逐渐取代晶体管保护技术,集成电路保护技术的研制、生产、应用的主导地位持续到90年代初。与此同时,我国从70年代末即已开始了计算机继电保护的研究,高等院校和科研院所起着先导的作用,相继研制了不同原理、不同型式的微机保护装置。1984年原华北电力学院研制的输电线路微机保护装置首先通过鉴定,并在系统中获得应用,揭开了我国继电保护发展史上新的一页,为微机保护的推广开辟了道路。在主设备保护方面,关于发电机失磁保护、发电机保护和发电机---变压器组保护、微机线路保护装置、微机相电压补偿方式高频保护、正序故障分量方向高频保护等也相继通过鉴定,至此,不同原理、不同机型的微机线路保护装置为电力系统提供了新一代性能优良、功能齐全、工作可靠的继电保护装置。随着微机保护装置的研究,在微机保护软件、算法等方面也取得了很多理论成果,此时,我国继电保护技术进入了微机保护的时代。

3.电力系统中继电保护的配置

继电保护主要利用电力系统中原件发生短路或异常情况时电气量(电流、电压、功率等)的变化来构成继电保护动作。继电保护装置的任务在于:在供电系统运行正常时.安全地、完整地监视各种设备的运行状况,为值班人员提供可靠的运行依据:供电系统发生故障时,自动地、迅速地、并有选择地切除故障部分,保证非故障部分继续运行:当供电系统中出现异常运行工作状况时,它应能及时、准确地发出信号或警报,通知值班人员尽快做出处理。

4.电力系统继电保护发展趋势

继电保护技术向计算机化、网络化、智能化、保护、控制、测量和数据通信一体化方向发展。随着计算机硬件的飞速发展,电力系统对微机保护的要求也在不断提高,除了保护的基本功能外,还应具有大容量故障信息和数据的长期存放空间,快速的数据处理功能,强大的通信能力,与其他保护,控制装置和调度联网以共享全系统数据,信息和网络资源的能力,高级语言编程等,使微机保护装置具备一台PC的功能。为保证系统的安全运行,各个保护单元与重合装置必须协调工作,因此,必须实现微机保护装置的网络化,这在当前的技术条件下是完全可行的。在实现继电保护的计算机化和网络化的条件下,保护装置实际上是一台高性能,为了测量、保护和控制的需要,室外变电站的所有设备,如变压器、线路等的二次电压、电流都必须用控制电缆引到主控室。所敷设的大量控制电缆投资大,且使得二次回路非常复杂。但是如果将上述的保护、控制、测量、数据通信一体化的计算机装置,就地安装在室外变电站的被保护设备旁,将被保护设备的电压、电流量在此装置内转换成数字量后,通过计算机网络送到主控室,则可免除大量的控制电缆。

5.继电保护装置简介、维护及实际应用

5.1.继电保护装置的简介

(1)WSTJ-1微机式继电保护数字通讯接口装置

这是近几年兴起的一种较为先进的继电保护装置,这套装置采用传统数字通信5群中的64kbi/s数据接口,但是却利用了最先进的专业光缆通道传输多路继电保护的开关量信号。

装置中的继电保护接口可与相间距离和零序方向保护配合,实现闭锁式或允许式保护逻辑,构成方向比较纵联保护。该装置可与微机线路保护配合,构成各种闭锁式和允许式保护。(2)继电保护装置的维护

(a)对新投运好和运作中的继电保护装置应按照《继电保护和电网安全自动装置检验条例》要求的项目进行检验;一般对10kV~35kV用户的继电保护装置,应该每两年进行一次检验,对供电可靠性较高的35kV及以上用户每年进行一次检验。(b)在交接班时应检查中央信号装置、闪光装置的完好情况,并检查直流系统的绝缘情况、电容储能装置的能量情况等。(c)对操作电源进行定期维护。(d)对继电器、端子排以及二次线将进行定期清扫、检查,此工作可以带电进行,也可以停电进行,但必须有两人在场,其中一人工作,一人监护;必须严格遵守《电业安全工作规程》中的有关要求,所用的工具应具备可靠绝缘手柄;清扫二次线上的尘土时,应由盘上部往下部进行;遇有活动的线头,应将其拧紧,以防止造成电流互感器二次回路、开路,而危及人身安全。

(3)全数字继电保护测试装置

全数字继电保护测试装置具有数字化、模块化、小型化、嵌入式人机界面等功能,主要技术特点为高压保护、测量装置等,满足IEC61850-9-1标准的数字量信号的情况下,从硬件结构和软件设计实现觉得保护装置的全数字操作目标。

整机采用两套DSP+CPLD分别作为信号发生和人机监控模块,其中主控DSP系统采用以太网模块和自定义的内部通信协议,通过模块间内部CAN通讯接口传输测试数据,而监控DSP系统赋予了整机人机交互和保护自检功能。该装置能够满足新型微机保护装置研发中对数字量继电保护测试数据的需要。

参考文献

篇5:电力系统继电保护现状及完善途径

摘 要:电力系统的继电保护成为我们电力网络正常运转和稳定进行的重要保障。然而,目前我国的继电保护还不够成熟,还存在很多的漏洞和弊端,我们应该加强控制直流电压脉动系数、加强一般性检验、改善定值区问题、保护装置检验,这样才能加强电力系统的安全性,文章针对电力系统继电保护的现状及完善途径作出了讨论。

关键词:电力系统;继电保护;现状;完善途径

前言

随着我国经济的不断发展,工业和生活上对电力能源的需求也在不断增加。而随着电力系统的不断复杂,电力网络的不断交叉,导致我们电路系统经常会出现不正常状况,因此,我们要加强继电保护设备的研究和应用。目前,我国在继电保护上还处于不成熟阶段,因此,要及时发现不足,并通过研究、学习,不断改进设备和完善继电保护系统。继电保护的现状

在19世纪后期,电力系统变的逐渐复杂,经常发生短路等故障,随着电力系统的发展,继电保护也开始逐步发展,一直到了20世纪初期,继电保护开始逐渐发展,出现了电磁型的继电保护装置,后来更多的静态继电器不断应用和生产,继电器广泛应用到电网系统中来,它具有较高的灵敏度及维护简单、消耗功率小、作速度、寿命长、体积小等优点,但是却容易受到干扰。

继电保护与高科技相结合。现代的继电保护技术已经随着科技不断改进,逐渐实现了网络化和测量、保护、数据通讯的一体化。网络作为信息和数据的通讯工具,将现代电力系统的安全和稳定相结合。现代的继电保护系统要求每个单元都能共享安全系统,因此可以在保护单元装置重合闸,对这些信息和数据进行处理和分析,将运行中的故障进行协调。实现这种继电保护就要将全部系统和计算机网络连接起来,实现微机保护装置网络化。但目前,我国在危机保护上还处于初级阶段,发展还比较不完善,因此需要加强科技的进步和工作人员的努力。

使用人工智能以及自适控制算法,进行继电保护。现在,人工智能技术已经被广泛的应用到继电保护系统中,这对比传统的方法,有着不可替代的作用。人工智能AI的思维逻辑和处理数据的能力都比较快,因此越来越多的AI被运用到电力系统中,尤其是在控制管理以及规划领域,发挥着重要的作用。另外,自适继电保护也逐渐应用于继电保护系统中,这是在20世纪80年代的开始出现的概念,它会根据继电运行方式中出现的错误和漏洞进行适当的改变保护性能和特征,也就是它可以适应各种情况的电力系统故障,这对于增强电力保护的可靠性,提高经济效益都有重要的作用。这种自适控制在变压器保护、发电机保护等领域已经广泛的使用。继电保护的作用和基本要求

2.1 作用

继电保护是整个电网系统的保护者,它是维护电力装置的安全和稳定运行的重要保障,它被形象的称为电网的“安全卫士”。当电力系统出现故障或者不正常的运转的情况下,继电保护就会对主控设备发出讯号,迅速、准确的判断故障系统元件并将它切除,保证电网的正常运作,同时发出的讯号可以使工作人员根据不正常的信号对电力系统的工作状态进行处理,保证了电力系统其他部分继续正常运转,减少安全事故。例如,当受到保护的元件由于一些不良情况发生故障时,继电保护会马上判断数据,并作出相应的反应,比如跳闸,这样就对不良元件进行了保护,同时,不影响其他部分正常运作,避免了突发状况带来的损失和后果。

2.2 基本要求

继电保护有选择性、灵敏性、速动性和可靠性等特点,这些也是他的基本要求,其中,可靠性是最根本的要求。可靠性主要是依靠继电保护的性能优良、装置正常、配置合理来维护和管理来保证的,这样可以使继电保护正常运行,保证由于提法状况导致的损失。其选择性说的是线路和设备首先进行自身的保护切除,进一步才对相邻的设备和线路进行保护切除,这是根据判断数据选择的。其灵敏性指的是当线路和设备发生金属短路时,继电保护可以及时、快速的进行反应,切除故障,具备必要的灵敏系数,这就是它的灵敏性。最后,它的速动性指的是,在线路发生故障时,能及时的切除线路的故障,从而减小事故的发生和损失。继电保护的完善途径

3.1 控制直流电压脉动系数

在直流系统中,直流电压脉动系数很大,导致晶体管和微机保护经常发生不正常运转的现象,我们可以将原硅整流装置改造为整流输出装置,这样输出交流分量小并且可靠性高,这样就形成集成电路硅整流充电装置。而对于平时阴雨天或雨季比较潮湿的天气情况之下,会发生直流失电的现象,这就需要将升压站户外端子箱中的易老化端子更换为陶瓷端子,这样可以提高二次绝缘,然后进行二次回路的整改,将控制、保护等步骤分开进行,随后查找直流失电的问题,安装熔断器分路开关箱,对避免直流失电起保护作用。而我国的电路规定电压是110kV、220kV,因此要将不满足要求的电网进行更换微机线路保护。

3.2 一般性检验

继电现场的一般性检验是继电保护很重要的一个环节,但是却常常被人忽略,这会给继电保护带来一定的隐患,因此,要加强对一般性检验的重视程度。一般性检验大概分为两个方面:首先,要清点连接件是否紧固,焊接点是否虚焊,机械特性是否良好等。由于目前我国继电保护的保护屏后方的端子排端子螺丝非常密且多,因此对于螺丝的加固就要严格检验,尤其是新安装的保护屏,经过运输和移动,大部分的螺丝已经有松动的现象,因此要在现场检验、确认,并且一个一个的将螺丝拧紧,否则可能出现因为保护拒动、误动造成的隐患。其次,我们还应该将继电保护装置上所有的插件卸下来,注意检验,看看是否有损坏,芯片是否拧紧,螺丝是否拧紧,以及焊接点是够虚焊。我们在检查中,还必须将每一个元件护屏、端子箱、控制屏的螺丝拧紧,把这件事作为一项重要的措施来落实。

3.3 定值区问题

现在的微机保护有一个优点,是可以有很多个定值区,在如今的电网运行方式的变化情况之下,定值更改问题成为了至关重要的问题。但是,我们还必须要注意的一个问题是,定值的错误会对微机保护产生重大的不良后果,这是微机保护的一个大忌。为了避免这种状况的发生,我们需要采取严格的管理手段和相应的技术手段来确保微机保护的定值的正确性。我们可以在定值修改完成后,打印定值单,并且标注好定值区号、变电站、注意日期、修改人员及设备名称,并且要在继电保护工作记录中明确的标注定制编号,加强每一环节的审核,这样可以减少错误的细节的数目,有利于保证这些数值的准确性和可靠性,这样对于域定值区的问题才可以圆满解决。

3.4 保护装置检验

我们在继电保护中,必须加强检验,这是对于继电保护设备良好运行的重要环节。我们在保护装置检验时,应该将电流回路升流实验和整组试验放在保护装置检验的最后进行,在检验完成有以后,还要严格禁止再拔插件、修改定值、改变定值区、改变二次回路等工作网。而电流回路升流实验和电压回路升压试验也是需要最后要完成的程序。同时,我们要进行定期的检验,在检验中,当设备进入被热状态或者是在检验完成以后,不能测负荷向量,也不能打印负荷采样值,同样的在投入运行而暂时没负荷的时候,也不能进行这两项活动,这是保证继电保护设备正常运行的必要方式。结束语

综上所述,在众多的能源中,电力能源作为一项重要的能源系统,在我们的生产、生活中不断运用。随着社会的发展,我们在电力系统继电保护上要不断加强研究,对现行的继电保护系统缺陷进行完善,然后不断改进继电保护设施,真正的做到使我们的电力网络系统的稳定和正常运行。继电保护系统作为我们电路的重要保证和安全卫士,将在未来发展的路途上不断完善和发展。

参考文献

篇6:电力系统继电保护及反事故措施

关键词: 继电保护

1.直流熔断器与相关回路配置

基本要求:(1)消除寄生回路;(2)增强保护功能的冗余度。1.1 直流溶断器的配置原则如下:

1.1.1 信号回路由专用熔断器供电,不得与其它回路混用。

1.1.2 由一组保护装置控制多组断路器(例如母线差动保护、变压器差动保护、发电机差动保护、线路横联差动保护、断路器失灵保护等)和各种双断路器的变电所结线方式(一又二分之一断路器、双断路器、角结线等):(1)每一断路器的操纵回路应分别由专用的直流熔断器供电。(2)保护装置的直流回路由另一组直流熔断器供电。

1.1.3 有两组跳闸线卷的断路器,其每一跳闸回路分别由专用的直流熔断器供电。

1.1.4 有两套纵联保护的线路,每一套纵联保护的直流回路应分别由专用的直流熔断器供电;后备保护的直流回路,可由另一组专用直流熔断器供电,也可适当地分配到前两组直流供电回路中。

1.1.5 采用“近后备”原则只有一套纵联保护和一套后备保护的线路,纵联保护与后备保护的直流回路应分别由专用的直流溶断器供电。1.2 接到同一熔断器的几组继电保护直流回路的结线原则:

(1)每一套独立的保护装置,均应有专用于直接到直流熔断器正负极电源的专用端子对,这一套保护的全部直流回路包括跳闸出口断电的线卷回路,都必须且只能从这一对专用端子取得直流的正和负电源。

(2)不答应一套独立保护的任一回路包括跳闸继电器,接到由另一套独立保护的专用端子对引进的直流正和负电源。(3)假如一套独立保护的继电器及回路分装在不同的保护屏上,同样也必须只能由同一专用端子对取得直流正和负电源。

1.3 由不同熔断器供电或不同专用端子对供电的两套保护装置的直流逻辑回路间不答应有任何电的联系,如有需要,必须经空接点输出。

1.4 找直流接地,应断开直流熔断器或断开由专用端子对在直流熔断器的联结,并在操纵前,先停用由该直流熔断器或由该专用端子对控制的所有保护装置;在直流回路恢复良好后再恢复保护装置的运行。

1.5 所有的独立保护装置都必须设有直流电源断电的自动告警回路。1.6 上、下级熔断器之间必须有选择性。

2.保护装置用直流中间继电器、跳(合)闸出口继电器及相关回路

2.1 直流电压为220V的直流继电器线卷的线径不宜小于0.09mm,如用线径小于0.09mm的继电器时,其线卷须经密封处理,以防止线卷断线,假如用低额定电压规格(如220V电源用110V的继电器)的直流继电器串联电阻的方式时,串联电阻的一端应接于负电源。

2.2 直流电压在110V及以上的中间继电器一般应有符合下面要求的消弧回路:(1)不得在它的控制接点以电容电阻回路实现消弧。

(2)不论是用电容或反向二级管并在中间继电器线卷上作消弧回路,在电容及二级管上串进数百欧的低值电阻,以防止电容或二级管短路时将中间继电器线卷回路短接。消弧回路应直接并在继电器线卷的端子上。

(3)选用的消弧回路用反向二级管,其反向击穿电压不宜低于1000V,尽不答应低于600V。

(4)注重因关联消弧回路而引起中间继电器返回沿时对相关控制回路的影响。2.3 跳闸出口继电器的起动电太不宜低于直流额定电压的50,以防止继电器线卷正电源侧接地时因直流回途经大的电容放电引起的误动作;但也不应过高,以保证直流电源降低时的可靠动作和正常情况下的快速动作。对于动作功率较大的中间继电器(例如5瓦以上)如为快速动作的需要,则答应动作电压略低于额定电压的50,此时必须保证继电器线卷的接线端子有足够的尽缘强度。假如适当进步了起动电压还不能满足防止误动作的要求,可以考虑在线卷回路上并联适当电阻以作补充。

由变压器、电抗器瓦斯保护起动的中间继电器,由于联线长,电缆电容大,为避免电源正极接地误动作,应采用较大起动功率的中间继电器,但不要求快速动作。2.4 断路器跳(合)闸线卷的出口接点控制回路,必须设有串联自保持的继电器回路,保证:

(1)跳(合)闸出口继电器的接点不断弧。(2)断路器可靠跳、合。

只有单出口继电器时,可以在出口继电器跳(合)闸接点回路中串进电流自保持线卷,并满足如下条件:

(1)自保持电流不大于额定跳(合)闸电流的一半左右,线卷压降小于5额定值。(2)出口继电器的电压起动线卷与电流自保持线卷的相互极性关系正确(3)电流与电压线卷间的耐压水平不低于交流1000V一分钟的试验标准(出厂试验应为交流2000V一分钟)。

(4)电流自保持线卷接在出口接点与断路器控制回路之间。

有多个出口继电器可能同时跳闸时,宜由防止跳跃继电器TBJ实现上述任务,防跳继电器应为快速动作的继电器,其动作电流小于跳闸电流的一半,线卷压降小于10额定值,并满足上述(2)~(4)项的相应要求。2.5 不推荐采用可控硅跳闸出口的方式。

2.6 两个及以上中间继电器线卷或回路并联使用时,应先并联,然后经公共联线引出。3.信号回路 3.1 应当装设直流电源回路尽缘监视装置,但必须用高内阻仪表实现,220V的不小于20千欧;110V不小于10千欧。

3.2 检查测试带串联信号继电器回路的整组起动电压,必须保证在80直流额定电压和最不利条件下分别保证中间继电器和信号继电器都能可靠动作。4.跳闸压板

4.1 除公用综合重合闸的出口跳闸回路外,其他直接控制跳闸线卷的出口继电器,其跳闸压板应装在跳闸线卷和出口继电器的接点间。

4.2 经过共用重合闸选相元件的220kV线路的各套保护回路的跳闸压板,应分别经切换压板接到各自起动重合闸的选相跳闸回路或跳闸不重合的端子上。4.3 综合重合闸中三相电流速断共用跳闸压板,但应在各分相回路中串进隔离二级管。

4.4 跳闸压板的开口端应装在上方,接到断路器的跳闸线卷回路;压板在落下过程中必须和相邻压板有足够的间隔,保证在操纵压板时不会碰到相邻的压板;检查并确证压板在扭紧螺栓后能可靠地接通回路;穿过保护屏的压板导电杆必须有尽缘套,并距屏孔有明显间隔;检查压板在拧紧后不会接地。不符合上述要求的需立即处理或更换。5.保护屏

5.1 保护屏必须有接地端子,并用截面不小于4平方毫米的多股铜线和接地网直接联通。装设静态保护的保护屏间应用专用接地铜排直接联通,各行专用接地铜排首末端同时联接,然后该接地网的一点经铜排与控制室按地网联通。专用接地铜排的截面不得小于100平方毫米。5.2 保护屏本身必须可靠接地。

5.3 屏上的电缆必须固定良好,防止脱落拉坏接线端子排造成事故。

5.4 所有用旋钮(整定用压板用)接通回路的端子,必须加铜垫片,以保护接通良好,非凡注重不因螺杆过长,以致不能可靠压接。5.5 跳(合)闸引出端子应与正电源适当地隔开。

5.6 到集成电路型保护或微机型保护的交流及直流电源来线,应先经抗干扰电容(最好接在保护装置箱体的接线端子上),然后才进进保护屏内,此时:(1)引进的回路导线应直接焊在抗干扰电容的一端上;抗干扰电容的另一端并接后接到屏的接地端子(母线)上。

(2)经抗干扰后引进装置在屏上的走线,应阔别直流操纵回路的导线及高频输进(出)回路的导线,更不得与这通些导线捆绑在一起。(3)引进保护装置逆变电源的直流电源应经抗干扰处理。

5.7 弱信号线不得和有强干扰(如中间继电器线卷回路)的导线相邻近。5.8 高频收发信机的输出(进)线应用屏蔽电缆,屏蔽层接地,接地线截面不小于1.5平方毫米。

5.9 两个被保护单元的保护装置配在一块屏上时,其安装必须明确分区,并划出明显界线,以利于分别停用试验。

一个被保护单元的各套独立保护装置配在一块屏上,其布置也应明确分区。5.10 集成电路及微机保护屏宜采用柜式结构。6.保护装置本体

6.1 保护装置的箱体,必须经试验确证可靠接地。

6.2 所有隔离变压器(电压、电流、直流逆变电源、导引线保护等)的一二次线卷间必

须有良好的屏蔽层,屏蔽层应在保护屏可靠接地。

6.3 外部引进至集成电路型或微机型保护装置的空接点,进进保护后应经光电隔离。

6.4 半导体型、集成电路型、微机型保护装置只能以空接点或光耦输出。7.开关场到控制室的电缆线 7.1 用于集成电路型,微机型保护的电流、电压和信号接点引进线,应采用屏蔽电缆,屏蔽层在开关场与控制室同时接地;各相电流和各相电压线及其中性线应分别置于同一电缆内。

7.2 不答应用电缆芯两端同时接地方法作为抗干扰措施。

7.3 高频同轴电缆应在两端分别接地,并紧靠高频同轴电缆敷设截面不小于100平方毫米两端接地的铜导线。

7.4 动力线、电热线等强电线路不得与二次弱电回路共用电缆。7.5 穿电缆的铁管和电缆沟应有效地防止积水。8.仪用互感器及其二次回路

8.1 电流互感器及电压互感器的二次回路必须分别有且只能有一点接地。8.2 由几组电流互感器二次组合的电流回路,如差动保护、各种双断路器主结线的保护电流回路,其接地点宜选在控制室。

8.3 经控制室 零相小母线(N600)联通的几组电压互感器二次回路,只应在控制室 将N600一点接地,各电压互感器二次中性点在开关场的接地点应断开;为保证接地可靠,各电压互感器的中性线不得接有可能断开的开关或接触器等。8.4 已在控制室一点接地的电压互感器二次线卷,如以为必要,可以在开关场将二次线卷中性点经放电间隙或氧化锌阀片接地,其击穿电压峰值应大于30Imax伏,Imax为电网接地故障时通过变电所的可能最大接地电流有效值,单位为千安。

8.5 宜取消电压互感器二次B相接地方式,或改为经隔离变压器实现同步并列。8.6 独立的、与其他互感器二次回路没有电的联系的电流或电压互感器二次回路,可以在控制室内也可以在开关场实现一点接地。

8.7 来自电压互感器二次的四根开关场引进线和互感器三次的两(三)根开关场引进线必须分开,不得公用。

8.8 多绕组电流互感器及其二次线卷接进保护回路的接线原则如下:(1)装小瓷套的一次端子应放在母线侧。

(2)保护接进的二次线卷分配,应非凡注重避免当一套线路保护停用(为了试验)而线路继续运行时,出现电流互感器内部故障时的保护死区。

8.9 新安装及解体检验后的电流互感器应作变比及伏安特性试验,并作三相比较以判别二次线卷有无匝间短路和一次导体有无分流;注重检查电流互感器末屏是否已可靠接地。

变压器中性点电流互感器的二次伏安特性需与接进的电流继电器起动值校对,保证后者在通过最大短路电流时能可靠动作。9.整流电源及储能电源

9.1 用整流电源作浮充电源的直流电源应满足下列要求:(1)直流电压波动范围应<±5额定值。(2)波纹系数<5(3)失往浮充电源后的最大负载下的直流电压不应低于80的额定值。9.2 新设计变电所,不应采用储能电源作操纵电源。对现有系统,其操纵电源应分为如下的各独立组,并定期作操纵试验。

(1)配出线瞬时动作保护一组,保证可同时供三台断路器跳闸和重合于永久性故障再可靠跳闸;此外,当线路故障使母线电压低于额定电压的60时,保护必须瞬时动作切除故障。

(2)配出线带时限动作的保护一组(瞬时与延时保护用同一出口继电器的例外)。(3)每台变压器保护一组,能同时跳开各侧断路器。(4)信号电源。

(5)试验用电源。不得以运行中的保护电源为试验电源。10.保护二次回路电压切换

10.1 用隔离刀闸辅助接点控制的电压切换继电器,应有一付电压切换继电器接点 作监视用;不得在运行中维护刀闸辅助接点。

10.2 检查并保证在切换过程中,不会产生电压互感器二次反充电。10.3 手动进行电压切换的,应有专用的运行规程,由运行职员执行。10.4 用隔离刀闸辅助接点控制的切换继电器,应同时控制可能误动作的保护的正电源;有处理切换继电器同时动作与同时不动作等异常情况的专用运行规程。11.保护原理

11.1 110kV及以上电压线路保护、包括各套保护装置间的相互配合,应按“四同一”

技术原则有组织地进行分类检查,凡属严重影响保护性能部分,应安排计划分期分批地进行更新或改进。

11.2 处理原有相间间隔保护不满足先单相后延时发展成两相不接地或对称三相短路情况下的无选择性跳闸的原则:(1)220kV线路一般由纵联保护保证。

(2)没有振荡题目的线路,非凡是110kV线路,要求间隔一、二段不经振荡闭锁控制。

(3)新设计的间隔保护,凡有可能的,宜增设不经振荡闭锁而用延时躲振荡的一、二段(或相应的功能)。11.3 重申如下原则:

(1)高频相差保护用两次比相。

(2)间隔保护用电流起动;振荡闭锁第一次起动后,只能在判别系统振荡平息后才答应再开放;间隔保护瞬时段在故障后短时开放。

(3)采用单相重合闸的线路,为确保多相故障时可靠不重合,宜增设由断路器位置继电器接点两两串联解除重合闸的附加回路。

11.4 采用相位比较原理的母差保护在用于双母线时,必须增设两母线先后接连发生故障时能可靠切除后一组母线故障的保护回路。11.5 远方直接跳闸,必须在相应的就地判据控制。11.6 不答应在强电源侧投进“弱电源回答”回路。

11.7 有独立选相跳闸功能的保护和经公用重合闸选相回路的保护装置共用时,前者仍应直接执行分相出口跳闸的任务;如有必要,可同时各用一组接点相互起动非全相运行的闭锁回路。

11.8 纵联保护的逻辑回路必须与通讯通道的特点和收发信机的特性相协调;对收发信机的输进/输出的工作信号时延特性、在通道各种强干扰信号下(包括故障点电弧产生的5MS左右的强干扰)可能丢失信号及误收信号的特性等直接影响继电保护安全性及可靠性的性能,提出明确的要求。

11.9 电压二次回路一相、两相或三相同时失压,都应发出警报,闭锁可能误动作的保护。

11.10 原设计要求用两组电压互感器二次电压构成的电压回路断线闭锁保护,假如只用一组电压互感器供电时,必须注重解决因此而带来的电压断线闭锁失效的题目。

11.11 双母线断路器失灵保护

除发电机变压器组的断路器非全相开断的保护外,均应设有足够灵敏度的电压闭锁控制多接点回路,闭锁接点应分别串接在各跳闸继电器接点中,不共用。为了适应降低电压闭锁元件的起动值的需要,应在零序电压继电器的回路中设三次谐波阻波回路。

11.12 采用三相电压自产零序电压的保护应注重当电压回路故障时同时失往相间及接地保护的题目。

11.13 所有发电机、变压器等的阻抗保护,都必须经电流起动,并应有电压回路断线闭锁。

11.14 电力载波答应式纵联保护只能用相一相耦合通道;但当发生多相故障时,原理上也可能拒动,应以此考虑配合要求。

11.15 采用解除闭锁式纵联保护,当反方向故障时,也必须提升导频功率至全功率,两侧时间配合关系要求与一般闭锁式一样。

11.16 实现单相重合闸的线路采用零序方向纵联保护时,应有健全相再故障时的快速动作保护。

11.17 重和闸应按断路器配置。

11.18 发电机变压器组的高压断路器、变压器的高压侧断路器、母线断路器和采用三相重合闸的线路断路器等均宜选用三相操纵的断路器。12.现场试验

12.1 必须要有明显的断开点(打开了压板或接线端子片等)才能确认,也只能确认在断开点以前的保护停用了;假如压板只控制本保护的出口跳闸继电器的线卷回路,则必须断开跳闸接点回路才能以为该保护确已停用。

对于采用单相重合闸,由压板控制正电源的三相分相跳闸回路,停用时除断开压板外,尚需断开各分相跳闸回路的输出端子,才能以为该保护已停用。12.2 不答应在未停用的保护装置上进行试验和其他测试工作;也不答应在保护未停用的情况下,用装置的试验按钮(除闭锁式纵联保护的起动发信按钮外)作试验。

12.3 所有的继电保护定值试验,都必须以符合正式运行条件(如加上盖子,关好门等等)为准。

12.4 分部试验应采用和保护同一直流电源,试验用直流电源应由专用熔断器供电。

12.5 只能用整组试验的方法,即除由电流及电压端子通进与故障情况相符的模拟故障量外,保护装置处于与投进运行完全相同的状态下,检查保护回路及整定值的正确性。不答应用卡继电器接点、短路接点或类似人为手段作保护装置的整组试验。12.6 对运行中的保护装置及自动装置的外部结线进行改动,即便是改动一根联线的最简单情况,也必须履行如下程序:

(1)先在原图上作好修改,经主管继电保护部分批准。

(2)按图施工,不准凭记忆工作;拆动二次回路时必须逐一作好记录,恢复时严格核对。

(3)改完后,作相应的逻辑回路整组试验,确认回路、极性及整定值完全正确,然后交由值班运行职员验收后再申请投进运行。

(4)施工单位应立即通知现场与主管继电保护部分修改图纸,工作负责人在现场修改图上签字,没有修改的原图应要求作废。

12.7 不宜用调整极化继电器的接点来改变其起动值与返回值;厂家应保证质量并应对继电器加封。

12.8 应对保护装置作拉合直流电源的试验(包括失压后短时接通及断续接通)以及直流电压缓慢地、大幅度地变化(升或降),保护在此过程中不得出现有误动作或信号误表示的情况。

12.9 对于载波收发信机,无论是专用或复用,都必须有专用规程按照保护逻辑回路要求,测试收发信回路整组输进/输出特性。

12.10 在载波通道上作业后必须检测通道裕量,并与新安装检验时的数值比较。12.11 新投进或改动了二次回路的变压器差动保护,在变压器由第一侧投进系统时必须投进跳闸,变压器充电良好后停用,然后变压器带上部分负荷,测六角图,同时测差回路的不平衡电流或电压,证实二次结线及极性正确无误后,才再将保护投进跳闸,在上述各种情况下,变压器的重瓦斯保护均应投进跳闸。12.12 所有差动保护(母线、变压器、纵差、横差等)在投进运行前,除测定相回路及差回路电流外,必须测各中性线的不平衡电流,以确证回路完整正确。12.13 对于集成电路型及微机型保护的测试应注重:(1)不得在现场试验过程中进行检验。

(2)在现场试验过程中不答应拔出插板测试,只答应用厂家提供的测试孔或测试板进行测试工作。

(3)插拔插件必须有专门措施,防止因人身静电损坏集成电路片;厂家应随装置提供相应的物件。

(4)必须在室内有可能使用对讲机的场所,用无线电对讲机发出的无线电信号对保护作干扰试验。假如保护屏是带有铁门封闭的,试验应分别在铁门封闭与打开的情况下进行,试验过程中保护不答应出现有任何异常现象。

12.14 在直流电源恢复(包括缓慢地恢复)时不能自动起动的直流逆变电源,必须更换。

12.15 所有试验仪表、测试仪器等,均必须按使用说明书的要求做好相应的接地(在被测保护屏的接地点)后,才能接通电源;注重与引进被测电流电压的接地关系,避免将输进的被测电流或电压短路;只有当所有电源断开后,才能将接地点断开。)12.16 所有正常运行时动作的电磁型电压及电流继电器的接点,必须严防抖动;非凡是综合重合闸中的相电流辅助选 相用的电流继电器,有抖动的必须消除或更换。

12.17 对于由3Uo构成的保护的测试:

(1)不能以检查3Uo回路是否有不平衡电压的方法来确认3Uo回路良好。(2)不能单独依靠“六角图”测试方法确证3U0构成的方向保护的极性关系正确。

(3)可以包括电流及电压互感器及其二次回路联接与方向元件等综合组成的整体进行试验,以确证整组方向保护的极性正确。

(4)最根本的办法,是查清电压及电流互感器极性,所有由互感器端子到继电保护盘的联线和盘上零序方向继电器的极性,作出综合的正确判定。12.18 变压器零序差动保护,应以包括两组电流互感器及其二次回路和继电器元件等综合组成的整体进行整组试验,以确证回路结线及极性正确。

12.19 多套保护回路共用一组电流互感器,停用其中一套保护进行试验时,或者与其他保护有关联的某一套进行试验时,必须非凡注重做好其他保护的安全措施,例如将相关的电流回路短接,将接到外部的接点全部断开等等。12.20 在可靠停 用相关运行保护的条件下,对新安装设备进行各种插拔直流熔断器的试验,以确证没有寄生回路存在。13.现场运行

13.1 纵联保护(如高频相差保护、高频闭锁方向保护等)的任一侧需要停用或停直流电源时(例如为了寻找直流电源接地等),必须先报调度,请求两侧都停用,然后才答应作业,作业完后,两侧保护按规定进行检查,并按规定程序恢复运行。13.2平行线的横差保护,当一侧的断路器断开,形成一回线送电、一回线充电的运行方式时,假如横差没有经检查邻线过电流控制,则两侧都应断开运行中一回线的横差保护的跳闸压板(即停用保护),但处于充电状态的一回线的压板不应断开(保护继续运行)。操纵顺序应在一次系统操纵完后,才往断开压板;恢复时先投压板然后进行一次系统操纵。

13.3 线路纵联保护每年的投进运行时间不得小于330天;配置双套纵联保护的线路,任何时候都应有一套纵联保护在运行中,非凡情况须经领导审批。13.4 线路基建投产,相应的保护包括纵联保护,必须同步投进运行。

13.5 电力线高频保护,必须天天交换通道信号,保护投进运行时收信裕量不得低于8.68db(以能开始保证保护可靠工作的收电平值为基值),运行中当发现通道传输衰耗较投运时增加超过规定值(3.0db)时,应立即报告主管调度通知有关部分,以判定高频通道是否发生故障、保护是否可以继续运行;运行中如发现通道裕量不足5.68db时,应立即通知上述调度机构请求将两侧纵联保护一起停用,然后才通知有关部分安排相应的检查工作。

13.6 答应式纵联保护的发信及收信信号和闭锁式纵联保护的收信信号应进行故障录波。

13.7 触动外壳时有可能动作的出口继电器,必须尽快更换。14.厂用电保护 各网、省局应结合运行经验分别制订相应的反事故措施,避免厂用电事故引起全厂停电。15.其他

15.1 为了保证静态保护装置本体的正常运行,最高的四周环境温度不超过 40℃,安装装置的室内温度不得超过 30℃,如不满足要求应装设空调设施。15.2 用水银接点的瓦期继电器必须更换。

15.3 三相三柱式变压器的零序阻抗必须以实测值为准。

15.4 故障录波器盘的电流电压回路及其接线端子等,必须满足继电保护二次回路质量要求,其接进电流应取自不饱和的仪表用的电流互感器的回路,否则取自后备保护的电流回路,并接到电流互感器二次回路末端。微机型故障录波器应按继电保护回路的尽缘和抗干扰要求进行试验。15.5 导引线电缆及有关接线应满足如下要求:(1)引进高压变电所开关场的导引线电缆部分,应采用双层尽缘护套的专用电缆,中间为金属屏蔽层,屏蔽层对外皮的耐压水平可选用15kV,50HZ,1分钟。(2)对于短线路,可以上述专用电缆直接联通两侧的导引线保护,但注重:(2)—1 供导引线保护用的芯线,必须确证是一对对绞线。不答应随便接进情况不明的其他两根线。

(2)—2 导引线电缆的芯线,接到隔离变压器高压侧线圈。隔离变压器的屏蔽层必须可靠地接进控制室地网,隔离变压器屏蔽层对隔离变压器高压侧线圈的耐压水平也应是15kV,50HZ,1分钟。所有可能触及隔离变压器高压侧的操纵,均应视为接触高压带电设备处理。

(2)—3 同一电缆内的其它芯线接进其它控制室设备时,也必须先经耐压水平15kV的隔离变压器隔离。不答应在变电所地网接地;更不答应出现两端接地的情况。

(2)—4 引到控制室的导引线电缆屏蔽层应尽缘,保持对控制室地网15kV的耐压水平;同时导引线电缆的屏蔽层必须在离开变电所地网边尚50—100米处实现可靠接地,以形成用大地为另一联接通路的屏蔽层两点接地方式。(3)对较长线路,可以只在引进变电站开关场部分采用双层尽缘护套的专用导引线电缆,并在距开关场地网边沿50—100米处接进一般通讯电缆。除遵守上一条原则外,并注重:

(3)—1 导引线保护用的一对通讯电缆芯线,也必须是对绞线。